OVEN ELECTRICAL REQUIREMENTS
FOR EACH OVEN:
A separate circuit breaker must be provided for each oven deck.
Electrical connections must be accessible when the ovens are in the installed position.
Electrical connections must meet all local code requirements.
Ensure ovens are grounded per local codes.
Incoming Power Connection Point
Control Box Rear - Standard
Earth Ground Lug
Ground Lug
Control Box Rear - World
Incoming Power Connection Point
Volts AC Amps Hertz Volts AC Amps Hertz Phase KW
1855 208/240/480 88/77/38 48 32
2440 208/240/480 75/65/33 41 27
3240 208/240/480 75/65/33 41 27
3255 208/240/480 88/77/38 48 32
3855 208/240/480 88/77/38 48 32
4 Wire Service - L1, L2, L3
5 Wire Service - L1, L2, L3
N +2 Grounds (per oven)
Electric Oven Electrical Requirements
Ground Lug